Intermittent Unable to Communicate Problem
1. To eliminate an interrupt request (IRQ) conflict, the most likely cause of
the problem, disconnect (or remove) the Management Card from the
UPS and restart PowerChute. If the problem persists, go to step 2, and
if the problem clears, go to step 3.
2. If the problem persisted, see your PowerChute documentation to
remove, and then reinstall, PowerChute. If the problem continues, see
APC Worldwide Customer Support for information about how to
contact
APC for technical support.
3. If the problem cleared, stop PowerChute.
4. Use an
ASCII text editor to edit the [ups] section of the PowerChute
initialization file (pwrchute.ini or powerchute.ini, depending on the
PowerChute operating system):
a. Add a
TimeoutFactor=40 parameter to the file.
b. Change the
UpsPollInterval value to =6 (default value is 4).
5. Reconnect (or reinstall) the Management Card and restart
PowerChute. If the problem continues, see APC Worldwide Customer
Support for information about how to contact
APC for technical support.