For example, if 3 minutes was the Maximum Shutdown Time setting
determined during the last negotiation process, and a new server has been
added to the Configured Client IP Addresses list that requires a 4-minute
shutdown delay, 4 minutes will be the Maximum Shutdown Time setting
at the end of the new negotiation process. Conversely, if none of the
servers need more than a 2-minute delay, 2 minutes will be the Maximum
Shutdown Time setting.
To view a flowchart presentation of the negotiation process,
see the
PCNS Maximum Shutdown Time Negotiation.pdf file
provided in the.\trouble\ directory on the APC Network
Management Card utility CD. The.\trouble\ directory also has
two other flowchart presentations that relate to PowerChute
network shutdown:
PCNS Shutdown Behavior.pdf and PCNS
Low-Battery Shutdown Behavior.pdf.