Operation: Respond to Alarms
26 InfraStruXure InRow RC—Operation and Maintenance
Upper Return Air Sensor Fault Critical • Make sure the sensor is connected properly.
• If the problem persists, replace the sensor, or contact
APC Worldwide Customer Support for assistance. Refer
to the back page of this manual for contact information.
Upper Supply Air Sensor Fault Critical • Make sure the sensor is connected properly.
• If the problem persists, replace the sensor, or contact
APC Worldwide Customer support. Refer to the back
page of this manual for contact information.
Water Detection Fault Warning • Identify the source of the leak.
• Isolate the leak by shutting off the main water supply
valve.
• For assistance, contact APC Worldwide Customer
support. Refer to the back page of this manual for
contact information.