29UPS Network Management Card 2 User’s Guide
(e.g., a UPS is already off when the Reboot UPS action starts), that UPS logs an event, and performs
the rest of the action, if any.
All participating UPS devices synchronize their performance of the action (within a one-second time
period under ideal conditions for Smart-UPS), but sometimes longer.
In reboot and sleep actions:
Immediately before the initiating UPS begins waiting the time specified as Return Delay, by
default it waits up to 120 seconds (its configurable Power Synchronized Delay) for any UPS that
does not have input power to regain that power.
Any UPS that does not regain input power during that delay does not participate in the
synchronized restart, but waits until its own input power returns before restarting.
The LEDs on the front of the UPS do not sequence their lights as they do for a normal (not
synchronized) reboot or sleep action.
UPS status and events are reported in the same way for synchronized actions as for actions on
individual UPS devices.
Guidelines for Synchronized Control Groups. Before you configure this UPS as a Synchronized Control
Group (SCG) member, review these guidelines:
All UPS devices in an SCG must be the same device.
SCGs are supported for any Smart-UPS with a card slot that accepts a Network Management Card.
When its membership in an SCG is enabled, the
NMC blocks UPS communications from a connected
management device on the serial communications port. However, the
NMC still allows access to the
command line interface on the serial communications port.
See also the Knowledge Base articles FA156114 and 11135, on the support website www.apc.com.
Display status of a Synchronized Control Group member. When SCG is enabled, the following
additional information is displayed about the SCG membership of this group mem
ber: its IP address, its Input
Status (Good is acceptable; Bad is not acceptable); and its Output Status (On or Off).
Field Description
Group
Membership
When you enable or disable Synchronized Control Group (SCG) membership, the change
causes the management interface to reboot the next time you log out, and is implemented at that
time.
The Sync Control option uses SNMPv3 for group communication. When you enable group
membership, SNMPv3 is enabled automatically.
Control Group
Number
The unique identifier of the SCG. This value must be a number from 1 through 65534. A UPS
can be a member of only one SCG. All members of an SCG must have the same Control Group
Number.
Multicast IP
Address
Specify the IP address used to communicate among members of an SCG. The allowed range is
224.0.0.3 to 224.0.0.254. All members must have the same Multicast IP Address.
Power
Synchronized
Delay
When the initiating UPS of the SCG is ready to turn on, this value is the maximum time that the
initiating UPS will wait, if necessary, for other group members to regain input power. (The
value is 120 seconds by default).
When this delay expires, the initiating UPS will wait to recharge its battery to the runtime
specified as Return Runtime Duration Offset (below), if necessary, then wait the time
specified as “Return Delay”, and then turn on.