115Installation Guide Silcon DP300E 208V/480V 10-80 kVA
7OY0002 US rev. 04
Action
Check fan, check for
airflow obstructions,
check for overload
As no. 20
As no. 20
As no. 20
As no. 20
Ensure battery
recharging
Save your data now
If repetitive call for
assistance
Call for assistance
Possible alarm
16. ** Q004 off **
17. ** Q003 on **
18. ** Q002 off **
19. ** Q001 or Q010 off **
20. High temp. isolation trans
former
21. High temp. mains static
switch
22. High temp. bypass static
switch
23. High temperature main
inverter
24. High temperature delta
inverter
25. Low DC shutdown
26. Low DC warning
27. Mains is moment. out of
tolerance
28. Mains is out of tolerance
29. Mains freq. is out of
tolerance
30. Bypass is moment out of
tolerance
31. Bypass is out of tolerance
32. Bypass freq. is out of
tolerance
33. Output is moment. out of
tolerance
34. Output is out of tolerance
Description
Position of output switch for
UPS in parallel
Position of external bypass
switch
Position of UPS output switch
Position of UPS input switch
Temperature on isolation
input/output transformer to
high
Temperature on static input
switch too high
Temperature on static bypass
switch too high
Temperature on main inverter
too high
Temperature on delta inverter
too high
The battery has been
discharged to minimum
permissionable level
The battery is nearly
decharged
Short disturbances on the
mains supply (1 ms tran-
sients)
Mains input voltage r.m.s.
value outside limits
Mains input frequency
outside limits
Short disturbances on the
bypass voltage
Bypass input voltage outside
limit
Bypass input frequency
outside limits
Short disturbances on the
output voltages
(inrush current)
Output voltage outside limits
Alarms