116 Installation Guide Silcon DP300E 208V/480V 10-80 kVA
7OY0002 US rev. 04
Alarms
Possible alarm
35. Output freq. is out of
tolerance
36. High battery temperature
37. Battery week
38. Battery defective
39. System is locked in oper.
mode
40 RAM1 memory write error
41. Memory write error
42. Communication to VQ
bypass lost
43. Communication to VQ
output lost
44. Communication to DMU
lost
45. Communication to control-
ler lost
46. Communication to parallel
IF lost
47. External shutdown
accepted
48. DC capacitor charge error
49. Communication to VQ
mains lost
50. Bypass sync error
Description
Output frequency outside
limits
To high battery ambient
temperature
Battery capacity below 75%
or battery MCB/fuse switched
off
Insufficient battery capacity or
battery MCB/fuse switched
off
UPS has attempted 10 times
within 1 min. to switch from
bypass to battery operation or
“High DC warning” has
appeared 10-20 times within
1 min.
Fault in UPS
Fault in UPS
Fault in UPS
Fault in UPS
Fault in UPS
Fault in UPS. Display will
show invalid data for UPS
Fault in UPS
Remote signal for switching
off the UPS accepted – UPS
switches off itself
Fault in DC charge circuit
Fault in UPS
The UPS cannot synchronize
to the bypass mains
Action
Call for assistance
Check system
ambient temp., check
fan, check for airflow
obstructions
Perform a battery
capacity test
Call for assistance
If the system is locked
in bypass operation
and the alarm “Inver-
ter voltage error”
exists in the alarm
stack do not try to
unlock the operations
mode lock but - call
for assistance!
Call for assistance
Call for assistance
Call for assistance
Call for assistance
Call for assistance
Call for assistance
Call for assistance
Do NOT insert fuse
F020 and F021 (or
close ext. MCCB) to
prevent damage of
UPS.
Call for assistance
Call for assistance
Check if phase rota-
tion of bypass voltage
is correct - if OK, call
for assistance