19Installation Guide Silcon DP300E 208V/480V 10-80 kVA
7OY0002 US rev. 04
Connection
Output
Ext. DC
Mains 1
Bonding jumper (See sec. 4.1.5.1)
NOTE:
Ensure correct phase rotation
of mains input voltage!!
Max. power cable size:
250 kcmil.
WARNING:
At 100% switch mode load the
neutral shall be rated for 173%
output phase current.
NOTE:
Glandplate in bottom of
system must be mounted.
NOTE:
This UPS is intended to be
supplied from a grounded
WYE-service, either 3 or 4 wire.
NOTE:
With 3 wire input, the UPS can
only be loaded 3 wire (phase to
phase.
NOTE:
All external cable dimensions
are recommended.
Please refer to local legal
provisions.
NOTE:
φ is symbol for “phase”.
is symbol for “risk of
electric shock”.
Terminal for Equipment
Grounding Conductor is
marked
Terminal for Grounding
Electrode Conductor is
marked “E”.
and
NOTE:
The terminals marked
are electrically connected to
the teminal marked „E“.
SYSTEM a) EXT. b) c) EXT. a) EXT. b) d) EXT. b) e) EXT. EXT. EXT. g) EXT. b) EXT.
INPUT INPUT OUTPUT OUTPUT NEUTRAL EQUIP. GROUND. BATTERY DC
FUSES PHASE FUSES PHASE CONDUC. GROUND. ELECTRO. MCCB CONDUC.
[A] CONDUC. [A] CONDUC. [AWG] CONDUC. CONDUC. [A] [AWG]
[AWG] [AWG] [AWG] [AWG]
DP315E
[208V] 60 4 45 6 2 10 8 100 2
DP320E
[208V] 80 2 60 4 1/0 8 8 100 2
DP330E
[208V] 125 2/0 90 1 4/0 6 6 125 1/0
DP330E
[480V] 50 4 40 6 3 10 8 100 2
DP340E 250
[208V] 150 4/0 125 2/0 kcmil 6 6 125 1/0
DP340E
[480V] 70 3 50 4 1 8 8 100 2
DP360E
[480V] 100 1/0 80 2 3/0 8 6 100 2
DP380E 250
[480V] 125 3/0 100 1/0 kcmil 6 6 125 1/0