27Installation Guide Silcon DP300E 208V/480V 10-80 kVA
7OY0002 US rev. 04
Connection
4.2 System Integration Interface
4.2.1 Introduction
Single Mains Input
The system Integration Interface (SII) is the control link between the UPS and the
system main switches as shown in the above diagram. The purpose is to ensure
correct operation of the switches without loosing the system output power.
Position information from auxiliary contacts on the main switches are the inputs for
the SII-board and the outputs are the lamp signals giving “the green light” for
operating the specific switches.
Besides above the SII-board also have input facilities for emergency shut down and
temperature compensation of the charge voltage for systems with external battery.
“Battery operation” and “Common fault” are the two main status relay signals also
coming from the SII-board.
NOTE:
Use of the same designations
in your diagrams make informa-
tion exchange much easier.