29Installation Guide Silcon DP300E 208V/480V 10-80 kVA
7OY0002 US rev. 04
Connection
4.3 Communication interface – ComInterface
4.3.1 Introduction
The ComInterface having 3 ports - is used when an interaction between UPS and
e.g. a computer system has to be established. The main purpose is to ensure a
controlled shut down of the computer in case of failures
in the mains supply.
4.3.2 Connections
X005, output relays:
The battery operation signal is 30 secs. delayed, but inhibited during battery tests.
The common fault relay is delayed. Standard factory setting is 10 secs. but other
periods can be programmed as described in 6.3.
Same phase as power source for the output relays is mandatory for voltages above
170V.
Terminals X001, X003, X005, X004, X012:
Cable size AWG18 to AWG14, use solid copper conductors only.
NOTE:
All alarm and signal circuit field
wiring shall be rated 300V
minimum.