40 Installation Guide Silcon DP300E 208V/480V 10-80 kVA
7OY0002 US rev. 04
Connection
4.7 Battery replacement
a. Servicing of batteries should be performed or supervised by personnel know-
ledgeable of batteries and the required precautions. Keep unauthorized person-
nel away from batteries.
b. When replacing the batteries in a system having internal batteries, it is de-
manded that the batteries are R/C (BAZR2).
Max. length each battery: 152mm
Max. width each battery: 67mm
When the batteries are to be mounted, there must be at least 0,5mm space
between the batteries and between the batteries and the battery shelf.
c. CAUTION - Do not dispose of battery or batteries in a fire. The battery may
explode.
d. CAUTION - Do not open or mutilate the battery or batteries. Released electro-
lyte is harmful to the skin an eyes. It may be toxic.
e. CAUTION - A battery can present a risk of electrical shock and high short
circuit current. The following precautions should be observed when working on
batteries:
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on top of batteries.
5. Disconnect charging source prior to connecting or disconnecting battery
terminals.
6. Determine if the battery is inadvertently grounded. If inadvertently
grounded, remove source of ground. Contact with any part of a grounded
battery can result in electrical shock. The likelihood of such shock will be
reduced if such grounds are removed during installation and maintenance
(applicable to a UPS and a remote battery supply not having a grounded
supply circuit).