61Installation Guide Silcon DP300E 208V/480V 10-80 kVA
7OY0002 US rev. 04
Options/Accessories
Bypass operation
: NO
Bypass operation
: YES
Display shows
WARNING!
If the UPS is out of service for
more than 8 days the
connected batteries might be
damaged. Refer to total
“Switching off“ as described in
Chapter 7.0.
Lamp indication
on bypass panel
Bypass operation
8.2.6.1 Bypassing the parallel UPS system
Action
Point 1-4 can be carried out with any of the parallel systems, however this will switch all
systems into bypass operation.
1. Press
on the keyboard
2. Press or on the keyboard until
3. Press on the keyboard
4. Press
on the keyboard
All systems will transfer to bypass operation
Do not switch off any of the UPS systems until
point 5-8 has been carried out
5. Check lamp indication on the bypass panel The green lamp (H003)
above the bypass switch
handle (Q003) lights
6. Turn the external bypass switch (Q003) The green lamp (H004)
to position “1“ above the output switch
(Q004) and the green lamps
(H002) above the output
switch handles (Q002) light
7. Turn the output switch (Q004) to position “0” The green lamps (H002)
above the output switch
(Q002) light and the green
lamp (H004) above the out-
put switch (Q004) lights
8. Turn all output switches (Q002) to position “0“ Now the lamps (H002) above
the output switch handles
(Q002) light and the green
lamp (H004) above the out-
put switch (Q004) lights
8.2.6 Operating the external service bypass switch for parallel systems
DP300E
DP300E
Q003
Service
bypass
switch
H003
Q001a
Q001b
Q002b
Q004
Q002a
LoadMains
H004
H002aH002b
Single Mains