65Installation Guide Silcon DP300E 208V/480V 10-80 kVA
7OY0002 US rev. 04
Options/Accessories
8.2.7 Isolating one UPS for service/maintenance
In a redundant system one UPS can be isolated for service/maintenance without
affecting the other parallelled UPS(s).
1. Check that the remaining UPS(s) will be able to carry the load when one UPS is
isolated.
2. Switch off the system to be isolated for maintenance by pushing the red “OFF”
push-button.
3. Disconnect battery, mains, and output by opening battery MCCB and turning
input switch (Q001) and output switch (Q002) to position “0”.
When Q002 is in position “0” the UPS can be operated and tested as a single
system without affecting the other parallelled UPS(s).
Switching back the UPS to normal parallel/redundant operation
1. Turn the input switch (Q001) and the output switch (Q002) to position “1”.
2. Charge capacitors, connect battery and start up the UPS as described in chapter
5.0.
The UPS will automatically switch to normal operation and start load sharing
with the other parallelled UPS(s).
WARNING!
The system will discharge built-
in capacitors. However, before
working on the system check
with a multimeter that there is
no dangerous voltage on the
terminals .
DP300E
DP300E
Q003
Service
bypass
switch
H003
Q001a
Q001b
Q002b
Q004
Q002a
LoadMains
H004
H002aH002b
Single Mains