76 Installation Guide Silcon DP300E 208V/480V 10-80 kVA
7OY0002 US rev. 04
Options/Accessories
8.5 Seismic anchoring
8.5.1 Mounting seismic anchoring without conduit box
8 holes for Ø10mm bolts have to be drilled according to dimensioned sketch, where
the UPS is going to be placed.
The 4 squares for seismic anchoring can be loosely tightened in the holes before the
UPS-system is placed. The system is placed, and then the squares are tightened in
the holes and in the feet of the UPS.
Or:
the system is placed after drilling the holes, and then the 4 squares are tightened in
the holes and the feet of the UPS. At a 39.37/1000 in./mm cubicle the seismic anchor-
ing can be bolted in the 4 outside feet or in the 2 middle feet and the 2 right or left
feet.
The square for seismic anchoring is placed towards the foot and bolted with bolt (1)
and plain washer (2) towards the foot and plain washer (2), string washer (3) and
nut (4) towards the square.
8.5.1.1 Seismic anchoring 23.62/600 in./mm cubicle mounted under frame
(measurements in mm)
IMPORTANT!
Remember to tighten all bolts in
the 4 squares, both in the floor
and in the feet of the UPS. Bolts
for the floor are not enclosed.
REAR SIDE
12
234
FRONT SIDE
40
40
625 ±2
705 ±2
4075 7540
260±2
490±2