83Installation Guide Silcon DP300E 208V/480V 10-80 kVA
7OY0002 US rev. 04
Options/Accessories
8.7 Remote display
8.7.1 Introduction
The remote display unit provides the Silcon DP300E series with the possibility to
display condition data at remote sites of up to 25 meters away from the Silcon
DP300E unit. For extension of communication distance, see section 8.7.1.1 below.
The remote display can easily be connected to the Silcon DP300E series via the serial
communication ports on the communication interface.
To obtain a transmission distance of 3.2 km the normal RS232C signal levels of the
serial in/out port must be converted to a 20mA current loop. The RS232C/20mA
converter must be placed outside the Silcon DP300E cubicle.
8.7.1.1 Extension of communication distance for remote display
The remote display communicates with the UPS through a 3 wire RS232 interface.
The remote display is a DTE (Data Terminal Equipment) employing a SUB-D 9 pole
female connector. The communication speed is 9,600 bps.
The communication distance is rather limited, see Table I. If a longer distance is
necessary or if the communication cable goes through magnetic noisy areas, it is
necessary to insert converters. Table 1 gives examples of three ways of increasing the
communication distance. All converters must be locally purchased.
Table 1: Examples of communication extension to remote display.
Standard RS485 Current Loop Optic fibre
(RS232)
Max. distance 25 meters 1,200 meters 3,200 meters 2,000 meters
Converter No converter
Manufacture BLACK BOX BLACK BOX BLACK BOX
Art. code IC 109A-E ME 800A-E ME540AE-ST
RS232 con- Sub-D 25 pole Sub-D 25 pole Sub-D 9 pole
nector on female female female
black box
Interconnector 4-screw 4-screw ST fibre
of black boxes terminal terminal terminal
Connections - without converter:
A 3 wire shield cable with a 25 pole female Sub-D and a 9 pole male Sub-D must be
made. Connect the cables as shown in Table 2. Do only connect the shield in one end.
Table 2: Pin connection for interconnection without converter.
25 pole female 9 pole male
Pin no. Pin no.
2 (TXD) 2 (RXD)
3 (RXD) 3 (TXD)
7 (GND) 5 (GND)
House No connection