Mass Configuration: Sensor and Alert Settings
130 InfraStruXure Central 4.0 User’s Reference
edit the label or history settings and then select Label/History Settings from the context menu.
3. Select one or more NetBotz devices from the device selection list and then click Edit.
4. Type in the Label field a label to identify this sensor. This label can be up to 64 characters in length,
and will be used to identify the sensor in alert notifications.
5. Select from the Sensor Value History drop box the total amount of time that data reported by this
sensor should be stored on the device. The total amount of data available on the device affects the
maximum amount of data that can be graphed.
6. Click OK to save the new Sensor values. Click Cancel to close this window without saving any
changes.
Numeric Sensors and Thresholds
The following Sensor & Alert Settings tasks enable you to configure thresholds on numeric-based
sensors:
Air Flow Settings
Amp Detector Settings
Audio Setting
Dew Point Settings
Humidity Settings
Power (VA) Settings
Power (Volts) Settings
Power (Watts) Settings
Temperature Settings
Other Numeric Settings
The following threshold types can be assigned to any numeric sensor:
Maximum Value Threshold: An alert condition occurs if the current sensor value exceeds a
specified acceptable value.
Minimum Value Threshold: An alert condition occurs if the current sensor value falls below a
specified acceptable value.
Range Threshold: An alert condition occurs if the current sensor value is not within a specified
range of acceptable values.
Above Value for Time Threshold: An alert condition occurs when the current sensor value exceeds a
specified value for a specified amount of time.
Below Value for Time Threshold: An alert condition occurs when the current sensor value falls
below a specified value for a specified amount of time.
Rate of Decrease Threshold: An alert condition occurs if the value reported by the sensor decreases
more than a specified amount within a specified amount of time.
Rate of Increase Threshold: An alert condition occurs if the value reported by the sensor rises more
than a specified amount within a specified amount of time.