Mass Configuration: Sensor and Alert Settings
146 InfraStruXure Central 4.0 User’s Reference
than the Maximum Increase value in a period of time that is equal to or less than the Time Period
value an alert condition is generated.
c. Check the Enabled check box to enable the threshold. If this check box is not checked, the alert
threshold will be saved but will not be active.
Add to the Threshold-Specific Addresses list the e-mail addresses of any personnel to whom e-
mail alert notifications should be sent if this threshold triggers an alert condition. Click Add...,
type in the e-mail address to which the alert notification will be sent, and then click OK.
If you’ve installed an SMS-capable modem you can deliver alert notification to SMS-enabled
devices by entering threshold-specific addresses for them in the following format:
sms:sms_device_address
where sms_device_address is the telephone number or e-mail address associated with the SMS-
enabled device (for example, “sms:5123334444” or “sms:[email protected]”).
6. If desired, specify Advanced Threshold settings. All Advanced threshold settings are optional. From
the Advanced tab in the Thresholds pane:
Specify a Return To Normal Delay value. Use the controls to specify the number of seconds that
must pass after this threshold has returned to normal before the threshold state is considered
returned to normal. Default value is 0 (state returns to normal immediately after the measured
value is no longer violating the threshold).
Set an Advanced Schedule for this threshold (optional). By default, all thresholds are assumed to
be enabled 24 hours a day, 7 days a week. However, you can specify that a threshold will be
enabled only during specific time ranges. To set an Advanced Schedule:
a.Click Advanced Schedule.... The Schedule Threshold window opens.
b.By default, all time periods in the schedule are set to Enabled. To disable the threshold for a
currently enabled period of time, highlight the period of time by clicking-and-dragging over the
desired time range, and then click Disable. To enable the threshold for a currently disabled
period of time, highlight the period of time by clicking-and-dragging over the desired time
range, and then click Enable.
c.When you have finished creating your Advanced Threshold, click OK to save the schedule and
return to the Thresholds task.
Select an Alert Severity value for this threshold. Available Alert Severities are, in order of
escalating severity: Information, Warning, Error, Critical, or Failure. By default, the Alert
Severity generated by this threshold will be “Error.”
Select Cameras to Trigger in response to the alert. To include images from one or more connected
NetBotz Camera Pod 120s, check the check boxes that correspond to the desired pods.
Specify a User-specified URL and User-specified Description. You can use these fields to include
additional user-specific information with any alert notifications that are generated using this
threshold.
Check the Return-To-Normal Requires User Input check box. When checked, if this threshold is
exceeded the sensor will not report a Return-To-Normal state until a user with Administrator or
Note
These threshold-specific notifications are sent only if your device has one or more Alert
Actions defined that use the Send E-Mail Message alert notification method and that have
the Include Addresses from Thresholds check box checked. For more information, see
“Alert Actions” on page 113 and “Creating Alert Actions” on page 221.