Display system configuration
Display system configuration
This function may be accessed from the initial
screen. Press the "*" button, followed by the "V"
button in less than one second.
Enter the password (a combination of four
buttons among the control panel buttons). If the
password is incorrect, the system displays the
following screen for a few seconds:
then automatically returns to the initial screen.
Selection of the type of display: local ("Monitor")
or distant ("Tele Monitor"). If the display is
distant, the local buzzer is deactivated.
Selection of display role on the network: master
(only one display may be the master) or slave.
Selection of the slave display number (multi-
display installation) from 1 to 10.
Selection of the numbers of the cubicles that the
display must control. Ten cubicle numbers are
successively presented. Select "yes" if the
display is to control the cubicle or "no" if it does
not control the cubicle or if the cubicle does not
exist. Confirm using the "*" button. The system
goes on to the next cubicle number. Following
confirmation of the last cubicle number, the
system automatically returns to the initial
screen.
Selection of the numbers of the slave displays
controlled by the master display. Ten display
number are successively presented. Select
"yes" if the master display is to control the slave
display or "no" if it does not control the display
or if the display does not exist. Confirm using
the "*" button. The system goes on to the next
display.
Selection of the numbers of the cubicles
controlled by the display. Eight cubicle number
are successively presented. Select "yes" if the
display is to control the cubicle or "no" if it does
not control the cubicle or if the cubicle does not
exist. Confirm using the "*" button. The system
goes on the next screen.
Confirmation as to whether the installation is
equipped with a giant screen. Following
confirmation using the "*" button, the system
automatically returns to the initial screen.
INCORRECT
PASSWORD
This function may be accessed from
the initial screen. Press the "*" button,
followed by the "V" button in less than
one second.
Note:
ensure that two "Monitor" or "Tele
Monitor" units do not receive the same
number;
only one master "Tele Monitor" may
be installed on the display network;
this function may be accessed only
with a password.
PASSWORD ?
=
DISPLAY = MASTER
>=SELECT =CONFIRM.
*
DISPLAY NUMBER =
>=SELECT =CONFIRM.
*
CUBICLE N° = YES
>=SELECT =CONFIRM.
*
*
initial screen
V
if display
is master
*
initial screen
DISPLAY N° = YES
>=SELECT =CONFIRM.
CUBICLE N° = YES
>=SELECT =CONFIRM.
*
GIANT DISPLAY =YES
>=SELECT =CONFIRM.
initial screen
*
if display
is slave
*
DISPLAY = LOCAL
>=SELECT =CONFIRM.
"Monitor" alphanumeric display (cont.)
Page view 45