APC MGE 6739380EN/JC User Manual Page 26

  • Download
  • Add to my manuals
  • Print
  • Page
    / 50
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 25
Page 26 - 6739380EN/JC
ABCDEFGH I JKLMN
12 3
4
5
11
Frequency converters
(no Mains 2)
Shutdown of the inverters results in the
interruption of the load;
shut down each inverter (see the
"shutdown of a unit" section);
open battery circuit breaker QF1 and
Mains 1 input switch Q1 on each unit;
the system is powered down (except
the Mains 1 cables upstream from
switch Q1). A full powering down
requires the opening of the upstream
protection device on Mains 1.
Parallel UPSs with SSC
(with Mains 2)
shut down each inverter (see the
"shutdown of a unit" section);
carry out the maintenance bypass
operation in the Static Switch Cubicle
(the load will be directly supplied by
Mains 2 via maintenance bypass switch
Q3BP);
close switch Q3BP and open
switches Q5N and Q4S in the "static
switch" cubicle;
open fuse switches Q1 and Q2 in the
Static Switch Cubicle;
open battery circuit breaker QF1 in
each UPS (except for frequency
converters without a battery);
open input switch Q1 for each UPS;
the UPSs are powered down (except
the Mains cables upstream from
switches Q1, Q4S and Q3BP) and the
load is supplied by Mains 2.
All the lights on the control panel are
off. A full powering down requires load
shutdown and the opening of the
upstream protection devices on
Mains 1 and 2.
Buzzer reset
first determine the cause of the
alarm;
press the "buzzer reset" button 11
on the hidden control panel on the
concerned cubicle.
The buzzer stops, but a new alarm will
set it off again.
Multi-bypass modular UPS
shutdown each UPS (see section
"shutdown of a unit");
the load is supplied via the Mains 2
of each UPS;
close switch Q3BP on each UPS, the
load is supplied by the Mains 2, via the
bypass lines (Q3BP) of each UPS;
open switches Q5N, Q4S, Q1 and
QF1 on each UPS, the situation is that
shown in the figure opposite;
the UPSs are de-energised once the
capacitors have discharged.
Q1
Q5N
QF1
Q3BP
Q4S
Q1
Q5N
QF1
Q3BP
Q4S
Modular UPS 2
Modular UPS 1
load
battery
inverter
mains 1
rectifier-
charger
static switch
battery
inverter
mains 1
rectifier-
charger
static switch
mains 2
Q1 Q5N
ON
OFF
(I)
(0)
ON
(I)
QF1
OFF
ON
(0)
(I)
Shutdown (cont.)