Site Planning: InfraStruXure 20kW System
12 InfraStruXure 20kW SystemInstallation, Operation, and Maintenance
Heat output
Consider the heat dissipation ratings of equipment to determine cooling requirements. Additional
equipment may be required.
Electrical requirements
Load Batteries fully charged Batteries charging
100% 6,345BTU/hr 9,346BTU/hr
75% 4,759BTU/hr 7,946BTU/hr
50% 3,172BTU/hr 6,360BTU/hr
Note 1: Batteries fully charged is a continuous rating; battery charge time is 3 hours,
maximum.
Note 2: Charging losses are based on 3000W, 90% charger electronic efficiency, and
80% battery charging efficiency.
Note
The heat output is higher while batteries are charging. Under normal operating
conditions, battery recharging periods are infrequent.
Upstream circuit breaker
(provided by customer)*
90A
Conductors to main input breaker
(provided by customer)*
208V, 4W + G
Recommended wire sizes 4AWG THHN
1-inch conduit
Torque for main input terminals 24.326in-lb
* Consult the NEC and local codes for sizing requirements.