Operation: Display Interface
42 InfraStruXure 20kW System: Installation, Operation, and Maintenance
Control screen
From the Control screen, you can select the following items:
Status screens
The Status screens display information regarding load, battery and power modules, voltage, and
current.
UPS into Bypass Place into or return from maintenance bypass operation.
Do Self Test Initiate a system of self-tests and diagnostics.
Simulate Power Fail Simulate a power failure.
Graceful Reboot Turn off and start load equipment in an orderly manner.
Graceful Turn Off Shut down load equipment in an orderly manner.
Start Runtime Cal Begin runtime calibration of the UPS.
Turn UPS Output On/Off Apply power to or shut down the system.
Status screen 1
Vin
Vout
Iout
The input voltage (V), output voltage (V), and output
current (A) for each phase (1–3).
Status screen 2
%load assuming no
redundancy
Percentage of the load in relation to the total capacity of all
power modules.
Status screen 3
%load allowing for
n+x redundancy
Percentage of the load, allowing for the redundancy in
your system.
Status screen 4
Frequencies The input and output frequency in hertz (Hz).
Status screen 5
Bat Voltage Actual voltage of the batteries (volts).
Bat Capacity Percentage of battery capacity available.
Runtime The available runtime for battery operation in hours and
minutes.
#Batts The number of installed battery modules.
#Bad The number of failed battery modules.