Operation: Display Interface
44 InfraStruXure 20kW System: Installation, Operation, and Maintenance
Accessories screen
The Accessories screen is used only if the display interface is connected to the computer interface
port on the Display/Computer Interface card on the InfraStruXure 20kW System. From the
Accessories screen, you can view the status of APC accessories connected to the UPS.
Output Freq Set the desired output frequency.
Alarms Redundancy: The state of redundancy that will trigger an alarm.
Choices are:
N+0an alarm will occur only when there is more load than all
functioning power modules can support
N+1an alarm will occur when there are no spare power
modules in good condition
N+2— an alarm will occur when there is only one functioning
power module
Load: When the load is greater than this threshold, an alarm will
sound.
Runtime: When the UPS is unable to power the load within the
parameters of the specified threshold, an alarm will sound. This alarm
is the result of an increase in load or a decrease in battery capacity.
Bypass Set the conditions that will automatically transfer the UPS into bypass
operation.
Copy Copy the UPS settings.
Other Self Test: Set the UPS to perform a self-test automatically at periodic
intervals.
UPS ID: Provide a unique name for the UPS.
VoutReporting: Set the reporting to the number of the tap to which the
most significant load is wired on the output transformer.
Output: Set the UPS output voltage.
BatFrAmpHour: Set the Amp-hour rating of external battery
enclosures that are not APC Symmetra XR Battery Enclosures.