Installation: Install the InfraStruXure 20kW System
InfraStruXure 20kW System: Installation, Operation, and Maintenance 17
2. Knock out the perforated hole in the gland plate for the conduit.
3. Install a lock-nut and bushing to the conduit.
4. Re-attach the gland plate, and then thread the conduit through the hole in the gland plate.
Install a utility circuit breaker. Before you connect the InfraStruXure 20kW System to utility, a
90A circuit breaker must be installed to protect the InfraStruXure 20kW System against over-current.
The circuit breaker must have a shunt trip.