Chapter 3:
How to Monitor a UPS
PowerNet MIB Reference Guide
13
[upsAdvIdent]
[upsBattery] UPS Battery OIDs
The [upsBattery] category has nine OIDs in two sub-categories, [upsBasicBattery] and
[upsAdvBattery] that provide UPS battery status information. Eight are read-only OIDs, and one OID
reports when the battery was replaced last, a value that you can define by using a SET.
You can access all nine OIDs through any Management Card or through a PowerNet Agent that
connects to the UPS through a smart-signalling cable. For a PowerNet Agent that connects to the UPS
through a simple-signalling cable, you can use only the three [upsBasicBattery] OIDs.
[upsBasicBattery]
OID Information Reported
upsAdvIdentFirmwareRevision The UPS firmware version.
upsAdvIdentDateOfManufacture The date on which the UPS completed the
manufacturing process.
upsAdvIdentSerialNumber The UPS serial number.
OID Information Reported
upsBasicBatteryStatus The current UPS battery status:
unknown (1): The Management Card or PowerNet Agent
cannot report the status.
batteryNormal (2): Within normal operating parameters.
batteryLow (3): Insufficient battery capacity to support the
UPS equipment load.
upsBasicTimeOnBattery The amount of time since the UPS switched to battery power.
upsBasicBatteryLastReplaceDate The date on which the battery was last replaced, a value you can
change by using a SET. The format is mm/dd/yy or mm/dd/yyyy.