APC AP9212 Technical Information Page 40

  • Download
  • Add to my manuals
  • Print
  • Page
    / 95
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 39
Chapter 4:
Integrated Environmental Monitor (iem) OIDs (AP9618 or AP9619 Network Management Card Only)
PowerNet MIB Reference Guide
33
[iemConfigProbes] OIDs
You use the following [iemConfigProbes] OIDs to view and change values used by the temperature
and humidity probe at an Integrated Environmental Monitor.
[iemConfigContacts] OIDs
You use the following [iemConfigContacts] OIDs to view and change values used by the input
contacts at an Integrated Environmental Monitor.
OID Task
iemConfigProbesNumProbes View whether the single probe is available (read-only).
{iemConfigProbesTable}
{iemConfigProbesEntry}
iemConfigProbeNumber
iemConfigProbeName
iemConfigProbeHighTempThreshold
iemConfigProbeLowTempThreshold
iemConfigProbeTempUnits
iemConfigProbeHighHumidThreshold
iemConfigProbeLowHumidThreshold
iemConfigProbeHighTempEnable
iemConfigProbeLowTempEnable
iemConfigProbeHighHumidEnable
iemConfigProbeLowHumidEnable
Access the set of OIDs for the probe and perform the
following:
View the number of the probe (read only).
Define a descriptive name for the probe.
Set the high-temperature threshold.
Set the low-temperature threshold.
View whether the probe uses Celsius (1) or
Fahrenheit (2) temperature values (read-only).
Note:
The temperature unit is defined by a system
preferences setting at the agent.
Set the high-humidity threshold.
Set the low-humidity threshold.
Enable or disable the following alarms:
- High-temperature threshold alarm
- Low-temperature threshold alarm
- High-humidity threshold alarm
- Low-humidity threshold alarm
OID Task
iemConfigContactsNumContacts View how many contacts are available (read-only).
{iemConfigContactsTable}
{iemConfigContactsEntry}
iemConfigContactNumber
iemConfigContactName
iemConfigContactEnable
Access the set of OIDs for each input contact and
perform the following:
Identify the contact to which this set of OIDs applies
(read-only).
Define a descriptive name for the contact.
Enable or disable the contact alarm.
Page view 39
1 2 ... 35 36 37 38 39 40 41 42 43 44 45 ... 94 95