Chapter 9:
Trap Severity Levels
PowerNet MIB Reference Guide
75
Trap Severity Levels
Each trap has one of the following severity levels.
How To Define Trap Receivers
Each Management Card, PowerNet Agent, MasterSwitch unit, and Automatic Transfer Switch can
send traps to as many as four trap receivers. You define an NMS as a trap receiver using that NMSs
IP address. You can also define other values for each trap receiver, such as the password (community
string) that traps must use when they are sent to a specific trap receiver.
To access the PowerNet MIB OIDs that you can use to define a trap receiver, perform these steps:
1. Select [apcmgmt] under [apc].
2. Select [mconfig].
Severe Warning Informational
Alerts a trap receiver of an
event that requires immediate
corrective action.
Alerts a trap receiver of an event that
can adversely affect a devices
operation if the situation worsens.
Alerts a trap receiver of an event
that can not adversely affect a
devices operation.
OID Task
mconfigNumTrapReceivers Identify the number of NMSs to receive traps (always 4).
{mconfigTrapReceiverTable}
{mconfigTrapReceiverEntry}
trapIndex
receiverAddr
communityString
severity
acceptThisReceiver
receiveTrapType
Use this tabled set of OIDs to define parameters for each trap
receiver:
Identify the trap receivers number (i.e. the read-only index to
the trap receiver entry).
Define the NMS as a trap receiver by the NMSs IP address. The
default value, 0.0.0.0, means that no NMS can receive traps.
Define the password (community name) a trap must use.
Identify the severity of traps to send to this NMS. Only traps of
a severity equal to or greater than this value are sent. See Trap
Severity Levels for definitions of the following severity levels:
-information (1)
-warning (2)
-severe (3)
Enable or disable sending traps to this NMS.
-yes (1): Enable sending traps.
-no (2): Disable sending traps.
Define the type of traps this NMS will receive. You must use
powernet (1) with a Management Card.