Chapter 8:
[atsStatus] Status OIDs
PowerNet MIB Reference Guide
68
[atsStatus] Status OIDs
The [atsStatus] category has six read-only OIDs that report the status of Automatic Transfer Switch components and
operation and one read-write OID that you can use to restart the recording of minimum and maximum values that
occurred for various operational parameters of the Automatic Transfer Switch.
OID Information Reported
atsStatusCommStatus The current communication status of the Automatic Transfer Switch:
atsNeverDiscovered (1), atsCommEstablished (2), or atsCommLost (3).
atsStatusSelectedSource The current source of power to the Automatic Transfer Switch: source A (1) or
source B (2).
atsStatusRedundancyState The Automatic Transfer Switchs current state of redundancy:
atsRedundancyLost (1): The Automatic Transfer Switch cannot switch to the
alternate power source if the power source that it is using fails.
atsFullyRedundant (2): The Automatic Transfer Switch can switch to the
alternate power source if the power source that it is using fails.
atsStatusOverCurrentState The state of the output current of the Automatic Transfer Switch:
atsOverCurrent (1): The Automatic Transfer Switch has exceeded the output
current threshold and cannot switch to the alternate power source if the source that
it is using fails.
atsCurrentOK (2): The output current is below the output current threshold.
atsStatus5VPowerSupply The current state of the Automatic Transfer Switchs 5-volt power supply:
atsPowerSupplyFailure (1): The power supply has failed, and the Automatic
Transfer Switchs internal Configuration menu, which you access through a
serial port connection, is not accessible.
atsPowerSupplyOK (2): The power supply is operating correctly (within
tolerance).
atsStatus24VPowerSupply The current state of the Automatic Transfer Switchs 24-volt power supply:
atsPowerSupplyFailure (1): The power supply has failed and the Automatic
Transfer Switch cannot switch to the alternate power source if the source that it is
using fails.
atsPowerSupplyOK (2): The power supply is operating correctly (within
tolerance).