Chapter 4:
Integrated Environmental Monitor (iem) OIDs (AP9618 or AP9619 Network Management Card Only)
PowerNet MIB Reference Guide
34
[iemStatus] OIDs
Three types of [iemStatus] read-only OIDs are available to view the status at an external
Environmental Monitor:
[iemStatusProbes] OIDs
[iemStatusContacts] OIDs
[iemStatusRelays] OIDs
[iemStatusProbes] OIDs
You use the following [iemStatusProbes] read-only OIDs to view information about the temperature
and humidity probes at an Integrated Environmental Monitor.
OID Information Reported
iemStatusProbesNumProbes The number of available probes
{iemStatusProbesTable}
{iemStatusProbesEntry}
iemStatusProbeNumber
iemStatusProbeName
iemStatusProbeStatus
iemStatusProbeCurrentTemp
iemStatusProbeTempUnits
iemStatusProbeCurrentHumid
iemStatusProbeHighTempViolation
iemStatusProbeLowTempViolation
iemStatusProbeHighHumidViolation
iemStatusProbeLowHumidViolation
Access the set of OIDs for each input contact and view
the following information:
The number of the probe
The name of the probe
The disconnected (1) or connected (2) status of the
probe
The current temperature reading at the probe
Whether Celsius (1) or Fahrenheit (2) temperature
values are used by the probe
Note:
The temperature unit used is defined by a
system preferences setting at the agent.
The current humidity reading at the probe
The noViolation (1), highTempViolation (2), or
disabled (3) status of the high-temperature alarm
The noViolation (1), lowTempViolation (2), or
disabled (3) status of the low-temperature alarm
The noViolation (1), highHumidViolation (2), or
disabled (3) status of the high-humidity alarm
The noViolation (1), lowHumidViolation (2), or
disabled (3) status of the low-humidity alarm