Chapter 4:
Integrated Environmental Monitor (iem) OIDs (AP9618 or AP9619 Network Management Card Only)
PowerNet MIB Reference Guide
34
[iemStatus] OIDs
Three types of [iemStatus] read-only OIDs are available to view the status at an external
Environmental Monitor:
• [iemStatusProbes] OIDs
• [iemStatusContacts] OIDs
• [iemStatusRelays] OIDs
[iemStatusProbes] OIDs
You use the following [iemStatusProbes] read-only OIDs to view information about the temperature
and humidity probes at an Integrated Environmental Monitor.
OID Information Reported
iemStatusProbesNumProbes The number of available probes
{iemStatusProbesTable}
{iemStatusProbesEntry}
iemStatusProbeNumber
iemStatusProbeName
iemStatusProbeStatus
iemStatusProbeCurrentTemp
iemStatusProbeTempUnits
iemStatusProbeCurrentHumid
iemStatusProbeHighTempViolation
iemStatusProbeLowTempViolation
iemStatusProbeHighHumidViolation
iemStatusProbeLowHumidViolation
Access the set of OIDs for each input contact and view
the following information:
• The number of the probe
• The name of the probe
• The disconnected (1) or connected (2) status of the
probe
• The current temperature reading at the probe
• Whether Celsius (1) or Fahrenheit (2) temperature
values are used by the probe
Note:
The temperature unit used is defined by a
system preferences setting at the agent.
• The current humidity reading at the probe
• The noViolation (1), highTempViolation (2), or
disabled (3) status of the high-temperature alarm
• The noViolation (1), lowTempViolation (2), or
disabled (3) status of the low-temperature alarm
• The noViolation (1), highHumidViolation (2), or
disabled (3) status of the high-humidity alarm
• The noViolation (1), lowHumidViolation (2), or
disabled (3) status of the low-humidity alarm