Chapter 6:
[sPDUOutletControlVM] Outlet Control OIDs
PowerNet MIB Reference Guide
48
[sPDUOutletControlVM] Outlet Control OIDs
The [sPDUOutletControlVM] category has a tabled set of OIDs that provide information on MasterSwitch VM unit’s
outlets and provide commands to control individual outlets.
OID Task
{sPDUOutletControlVMTable}
{sPDUOutletControlVMEntry}
sPDUOutletControlVMIndex
sPDUOutletControlVMName
sPDUOutletControlVMOutletIndex
sPDUOutletControlVMOutletName
sPDUOutletControlVMOutletCommand
Control a specified outlet. (The sPDUMasterStatusVMOutletCount
OID identifies the number of table entries.)
• The index to the MasterSwitch VM unit’s entry (read-only).
• The name of the MasterSwitch VM unit (read-only). (You use the
sPDUMasterConfigVMName OID to define this name.)
• The outlet number (read-only).
• The name of the outlet (read-only). (You use the
sPDUOutletConfigVMOutletName OID to define this name.)
• Obtain the outlet state by using a GET:
- immediateOnVM (1) if the outlet is on.
- immediateOffVM (2) if the outlet is off.
Perform any of the following by using a GET.
- immediateOnVM (1): Immediately turn on outlet.
- immediateOffVM (2): Immediately turn off the outlet.
- immediateRebootVM (3): immediately reboot the outlet.
- delayedOnVM (4): Turn on the outlet after the time specified by
the
sPDUOutletConfigVMPowerOnTime OID.
- delayedOffVM (5): Turn off the outlet after the time specified by
the
sPDUOutletConfigVMPowerOffTime OID.
- delayedRebootVM (6): Perform the command delayedOffVM,
wait the time specified by the
sPDUOutletConfigVMRebootDuration OID, and then perform
the command immediateOnVM.
- cancelPendingCommandVM (7): Cancel any pending command
to the outlet.