Chapter 7:
[sPDUMasterControlMSP] Master Control OIDs
PowerNet MIB Reference Guide
53
[sPDUMasterControlMSP] Master Control OIDs
The [sPDUMasterControlMSP] category has a read-only OID and a tabled set of OIDS that provide information on the
MasterSwitch Plus unit and commands to control it.
OID Task
sPDUMasterControlMSPTableSize The number of MasterSwitch Plus units.
{sPDUMasterControlMSPTable}
{sPDUMasterControlMSPEntry}
sPDUMasterControlMSPIndex
sPDUMasterControlMSPName
sPDUMasterControlMSPCommand
View and control a specified MasterSwitch Plus unit.
The index to the MasterSwitch Plus units entry (read only).
The name of the MasterSwitch Plus unit (read only) (You use the
sPDUMasterConfigMSPName OID to define this name).
Affect the current outlet state.
- noCommandAllMSP (1): The value returned by an SNMP GET of
this OID.
- immediateAllOnMSP (2): Turn on all outlets immediately.
- sequencedAllOnMSP (3): Turn on all outlets as defined by the
sPDUOutletConfigMSPgsPowerOnDelay OID for each outlet.
- immediateAllOffMSP (4): Turn off all outlets immediately.
- gracefulAllRebootMSP (5): After the device running PowerChute
plus confirms shutdown, reboot all outlets as defined by the time
value of the sPDUOutletConfigMSPgsRebootDuration OID for
each outlet.
- immediateAllRebootMSP (6): Reboot all outlets immediately.
- gracefulAllShutdownMSP (7): After the device running
PowerChute plus confirms shutdown, shut down all outlets as defined
by the time value of the sPDUOutletConfigMSPgsPowerOffDelay
OID for each outlet. Turn each outlet back on after waiting for two
consecutive delay periods:
The time defined by the value of the OID
sPDUOutletConfigMSPgsRestartDelay for the
outlet
The time defined by the value of the OID
sPDUOutletConfigMSPgsPowerOnDelay for the
outlet.
- overrideAllBatCapThreshMSP (8): Ignore the battery capacity
threshold, and turn on each outlet after the delay defined by the
sPDUOutletConfigMSPgsPowerOnDelay OID for that outlet.
- cancelAllPendingCommandsMSP (9): Cancel all pending
commands on the MasterSwitch Plus unit.
- restoreFactoryDefaultsMSP (10): Reset the settings for the
MasterSwitch Plus unit to the defaults originally set at the factory.