Chapter 5:
[sPDUOutletControl] Outlet Control OIDs
PowerNet MIB Reference Guide
41
[sPDUOutletControl] Outlet Control OIDs
The [sPDUOutletControl] category has a read-only OID and a tabled set of OIDs.
OID Task
sPDUOutletControlTableSize
Identify the number of MasterSwitch unit outlets (always 8)
{sPDUOutletControlTable}
{sPDUOutletControlEntry}
sPDUOutletControlIndex
sPDUOutletPending
sPDUOutletCtl
sPDUOutletCtlName
View and control each outlet individually:
• The outlet number (read-only).
• Identify whether the outlet has a command pending:
- commandPending (1): A command is pending.
- noCommandPending (2): There is no pending command.
- commandPendingUnknown (3): This is an error condition. To clear the
condition, shut down all devices powered by the MasterSwitch unit, and turn
power off and then on to the MasterSwitch unit.
• Affect the outlet’s current operation.
- outletOn (1): Turn on the outlet’s power.
- outletOff (2): Turn off the outlet’s power.
- outletReboot (3): Turn off and then turn on the outlet’s power.
- outletUnknown (4): This is an error condition. Shut down all devices powered
by the MasterSwitch unit, then turn power off and on to the MasterSwitch unit
to clear the condition.
- outletOnWithDelay (5): Not valid for firmware version 1.x. Turn on the
outlet’s power after the delay specified as sPDUOutletPowerOnTime.
- outletOffWithDelay (6): Not valid for firmware version 1.x. Turn off the
outlet’s power after the delay specified as sPDUOutletPowerOffTime.
- outletRebootWithDelay (7): Not valid for firmware version 1.x. After the
delay specified as sPDUOutletPowerOffTime, turn off the outlet’s power,
wait the time specified as sPDUOutletRebootDuration, and turn on the
outlet’s power.
• Identify the outlet’s name (20 characters or less) as defined by
sPDUOutletName. See [sPDUOutletConfig] Outlet Configuration OIDs.