APC AP9212 Technical Information Page 49

  • Download
  • Add to my manuals
  • Print
  • Page
    / 95
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 48
Chapter 5:
[sPDUOutletConfig] Outlet Configuration OIDs
PowerNet MIB Reference Guide
42
[sPDUOutletConfig] Outlet Configuration OIDs
The [sPDUOutletConfig] category has a read-only OID and a tabled set of OIDs.
OID Task
sPDUOutletConfigTableSize
Identify the number of MasterSwitch unit outlets (always 8).
{sPDUOutletConfigTable}
{sPDUOutletConfigEntry}
sPDUOutletConfigIndex
sPDUOutletPowerOnTime
sPDUOutletName
sPDUOutletPowerOffTime
sPDUOutletRebootDuration
View and configure each outlet individually.
The outlet number (read-only).
Define how long the outlet will wait to provide output power after the
MasterSwitch unit is turned on.
- -1: Never start providing output power automatically.
- 0: Begin providing output power immediately.
- 15: 15-second delay
- 30: 30-second delay
- 45: 45-second delay
- 60: 1-minute delay
- 120: 2-minute delay
- 300: 5-minute delay
Define a name of up to 20 characters for the outlet.
Not valid for Firmware version 1.x. Define the time that the outlet will wait
after being commanded to turn off its output power until it does turn off its
output power
- -1: Never stop providing output power automatically
- 0: Stop providing output power immediately.
- 15: 15-second delay
- 30: 30-second delay
- 45: 45-second delay
- 60: 1-minute delay
- 120: 2-minute delay
- 300: 5-minute delay
Not valid for Firmware version 1.x. Define how long a delay will occur after
power is turned off during a reboot sequence until power is turned on again.
- 5: 5-second delay
- 10: 10-second delay
- 15: 15-second delay
- 20: 20-second delay
- 30: 30-second delay
- 45: 45-second delay
- 60: 1-minute delay
Page view 48